Category: Main page » Power Circuits

UPS YUNTO P Series (250/500/750/1250)

pinout

9 pin D-SUB female
9 pin D-SUB female connector  at the UPS
Pin Name Dir Description
1Battery ModeoutThis pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN)
2---
3---
4---
5Ground-Ground terminal and common root of contacts at PIN 1, 8 and 9
6---
7UPS shut-downINIf a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground)
8Battery Capacity LowOUTThis pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN)
9Battery ModeOUTThe connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED)

Note: Direction is relative to UPS.

Source:www.pinouts.ru


This page no comment. You can be the first.

Your name:
Your Email:

Comment:
Type the characters: *
captcha
Refresh